Capacitor Bank Protected by Fuses

 

Where external protection of the capacitor units from long-term overloading or short-circuiting is to be provided, a value between 1.43 and 1.8 times rated current should be adopted. The fuses should be of the slow-blowing type owing to the high momentary current at make.

 Output Unit/ Equipment (kVAr)

Rated Capacitance (µF)

Rated Current (Amps)

Cross section for 4/C Cu cable (mm2)

Fuse Current Slow-blow (Amps)

 

10

3 x 66.3

14.4

4

25

 

12.5

3 x 82.9

18.0

6

35

 

15

3 x 99.5

21.6

6

35

 

20

3 x 132.6

28.8

10

50

 

25

3 x 165.8

36.1

16

63

 

30

3 x 198.9

43.3

25

80

 

40

3x 265.3

57.7

35

100

 

50

3 x 331.6

72.1

50

125

 

60

3 x 397.6

86.6

70

160

 

70

3 x 464.2

101

70

160

 

90

3 x 596.8

130

120

250

 

100

3 x 663.1

144

120

250

 

125

3 x 828.9

180

185

300

 

150

3 x 994.7

217

240

315

 

180

3 x 1193.7

260

240

400

 

200

3 x 1326.3

280

240

400

 

250

3 x 1657.9

361

240

400

 

300

3 x 1989.4

433

400

630

 

 

 Connecting cables should be designed for 1.5 times the rated current values and upwards.

 

The diameter for cables and the fuse ratings are minimum values valid for operation under normal conditions and at an ambient temperature of 300C; higher values shall be selected if conditions differ from normal (e.g. in case of harmonics).